RN SERIES
Packaged Rooftop Units, Heat Pumps,
& Outdoor Air Handling Units
Installation, Operation,
& Maintenance
o Do not store gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance
o WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
use any phone in your building.
Leave the building immediately.
gas supplier’s instructions.
the fire department.
o Startup and service must be performed by a
Factory Trained Service Technician.
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings
exactly could result in serious
injury, death or property damage.
Be sure to read and understand
the installation, operation, and
service instructions in this manual.
Improper installation, adjustment,
alteration, service, or maintenance
can cause serious injury, death, or
property damage.
A copy of this IOM should be kept
with the unit.
WARNING
Vue de la page 0
1 2 3 4 5 6 ... 115 116

Résumé du contenu

Page 1 - RN SERIES

RN SERIES Packaged Rooftop Units, Heat Pumps, & Outdoor Air Handling Units Installation, Operation, & Maintenance

Page 2

10 UNIT HANDLING To prevent injury or death lifti

Page 3 - Table of Contents

100 Table 47 - 26, 31-50, 60, and 70 ton Energy Recovery Wheel Filters Feature 1A Quantity / Size Type F, G, H, J, Q, R, S, T, U, V, W, Y, Z, 1, 2, 3

Page 4

101 20” 20” 16” 16” Figure 51 - RN Series 6-8 and 10 ton Standard Filter Layout (Viewed from the Upstream Side of the Cooling Coil) 25” 25” 2

Page 5

102 20” 20” 20” 25” 25” Figure 53 - RN Series 16-25 and 30 ton Standard Filter Layout (Viewed from the Upstream Side of the Cooling Coil) 2

Page 6

103 24” 24” 24” 24” 12” 12” 12” Figure 55 - RN Series 50-, 60, and 70 ton Standard Filter Layout (Viewed from the Upstream Side of the

Page 7

104 20” 20” 20” 20” 20” 16” 24” 24” 24” Figure 57 - RN Series 55, 65, and 75 ton Standard Filter Layout, 4” Filters (Viewed from

Page 8

105 20” 20” 20” 20” 20” 20” 20” 16” 24” 24” 24” Figure 59 - RN Series 90-140 ton Standard Filter Layout, 4” Filters and

Page 9

106 Appendix A - Heat Exchanger Corrosion Resistance Corrosion Resistance of Copper and Stainless Steel in Brazed Plate Heat Exchangers - Points to

Page 10

107 Water Containing Concentration (mg/l or ppm) Time Limits - Analyze Before AISI 316 SMO 254 Copper Alloy Nickel Alloy Total Hardness (°dH) 4.0-8.5

Page 11

108 Appendix B - Thermistor Temperature vs. Resistance ValuesDeg C Deg F Resistance (kOhms) -40 -40 2889.6 -35 -31 2087.22 -30 -22 1522.20 -25 -13 11

Page 12

109 RN Series Startup Form Date:______________ Job Name:_____________________________________________________________________ Address:______________

Page 13

11 1. Startup and service must be performed by a Factory Tr

Page 14

110 Energy Recovery Wheel Assembly Wheel(s) Spin Freely Check Rotation FLA____________ Number hp L1 L2 L3 1 2 Power Return/E

Page 15 - Model Option B: HEATING

111 Refrigeration System 1 – Cooling Mode Pressure Saturated Temperature Line Temperature Sub-cooling Superheat Discharge N/A N/A Suction N/A

Page 16

112 Refrigeration System 4 – Heating Mode (Heat Pump only) Pressure Saturated Temperature Line Temperature Sub-cooling Superheat Discharge N/A N/

Page 17

113 Electric Preheating Limit Lockout Aux. Limit Lockout Outside Air Temperature Setpoint ________°F Preheat Leaving Air Temperature Setpoint _

Page 18 - Feature 6: FILTERS

114 Literature Change History May 2007 Update of IOM unit service clearances. Length of front and back clearances from 60” to 48” and length of lef

Page 19

115 April 2011 Updated the condenser water connection sizes in Table I12 and added Table I13 – SMO 254 Brazed Plate Heat Exchanger Water Connections

Page 20

AAON 2425 South Yukon Ave. Tulsa, OK 74107-2728 Phone: 918-583-2266 Fax: 918-583-6094 www.aaon.com RN Series Installation, Operation & M

Page 21

12 4. Provide adequate combustion ventilation air to the furnace. If a vent duct extension is used, a class III approved vent is requir

Page 22

13 RN Series Feature String Nomenclature BASE MODEL SERIES AND GENERATION RN UNIT SIZE 006 = 6 ton Capacity 007 = 7 ton Capacity 008 = 8 ton Capa

Page 23

14 RN Series Feature String Nomenclature Model Option A: COOLING/HEAT PUMP A3: COIL COATING 0 = Standard 1 = Polymer E-Coated Evap. and Cond. 2 = St

Page 24 - CAUTION

15 RN Series Feature String Nomenclature B2: HEATING DESIGNATION 0 = No Heating 1 = Heat 1 2 = Heat 2 3 = Heat 3 4 = Heat 4 6 = Heat 6 7 = Heat 7 8

Page 25

16 RN Series Feature String Nomenclature Feature 1: RETURN/OUTSIDE AIR 1B: RETURN/EXHAUST AIR BLOWER CONFIGURATION 0 = Standard – None A = 1 Blower

Page 26

17 RN Series Feature String Nomenclature Feature 2: OUTSIDE AIR CONTROL 0 = Standard - None A = 3 Position Actuator - Sensible Limit B = 3 Position

Page 27

18 RN Series Feature String Nomenclature Feature 5: SUPPLY AIR OPTIONS 5A: SUPPLY AIR BLOWER CONFIGURATION 0 = 1 Blower + Standard Eff. Motor A = 2

Page 28

19 RN Series Feature String Nomenclature 6C: FILTER OPTIONS 0 = Standard A = Clogged Filter Switch B = Magnehelic Gauge C = Options A + B Feature

Page 30 - Installation

20 RN Series Feature String Nomenclature Feature 11: SAFETY OPTIONS 0 = Standard A = Return and Supply Air Firestat B = Return Air Smoke Detector C

Page 31

21 RN Series Feature String Nomenclature Feature 13: SPECIAL CONTROLS 0 = Terminal Block for Thermostat Control D = VAV Unit Controller - VAV Cool

Page 32

22 RN Series Feature String Nomenclature Feature 18: CUSTOMER CODE 0 = Standard Feature 19: CODE OPTIONS 0 = Standard - ETL U.S.A. Listing B = Chi

Page 33

23 RN Series Feature String Nomenclature Feature 23: TYPE B = Standard - AAON Gray Paint U = Special Pricing Authorization + Special Paint X = Spec

Page 34

24 General Information RN Series packaged rooftop units, heat pumps and outdoor air handling units have been designed for outdoor installation

Page 35

25 Installation of RN Series units must conform to the ICC standards of the International Mechanical Code, the International Building Code, an

Page 36

26 Figure 1 - Lockable Handle The warranty card must be completed in full and returned to AAON not more than 3 months after unit is delivere

Page 37

27 Never cut off the main power supply to the unit, except for servicing, emergency, or complete shutdown of the unit. When power is cut off

Page 38

28 Should overheating occur with a gas heat exchanger, or the gas supply fail to shut off, shut off the manual gas valve to the furnace before

Page 39

29 Wiring Diagrams Unit specific wiring diagrams are laminated and affixed inside the controls compartment door. Condensate Drain Pan Unit requires

Page 40

Table of Contents Safety ...

Page 41

30 Installation AAON equipment has been designed for quick and easy installation. Locating Units The curb should be mounted first and must be

Page 42

31 Table 4 - C Cabinet Unit Clearances Location Unit Size 16-25 and 30 tons Front - (Controls Side) 48” Back - (Outside Air) 48” *Left Side *21” Rig

Page 43

32 Be careful to install the provided neoprene gasket according to the following figure prior to setting the unit on the curb.

Page 44

33 Figure 5 - RN Series 6-8 and 10 ton Unit Gasket Locations

Page 45

34 Figure 6 - RN Series 9 and 11-15 ton Unit Gasket Locations

Page 46

35 Figure 7 - RN Series 16-25 and 30 ton Unit Gasket Locations

Page 47

36 Figure 8 - RN Series 26, 31-50, 60, and 70 ton Unit Gasket Locations

Page 48

37 Forklifting the Unit (6-25 and 30 ton) 6-25 and 30 ton units can be lifted using a forklift. 9, 11-25 and 30 ton units must have forks 72”

Page 49

38 with the outside air hood in the open position. Before lifting unit, be sure that all shipping material has been removed from unit. Secure

Page 50

39 Figure 11 - Lifting Details of a 6-25 and 30 ton Energy Recovery Wheel or Power Return Unit Figure 12 - Lifting Details of a 26, 31-50, 60 and

Page 51

4 Checking Liquid Sub-Cooling ... 76 Checking Evaporator S

Page 52

40 Figure 13 - Lifting Details of a 55, 65 and 75-140 ton Unit

Page 53

41 Duct Connection Note: If outside air will be in contact with the air tunnel base of an A, B or C cabinet unit (6-25 and 30 tons), the unit

Page 54

42 Seismic Curb Installation Using a standard curb with a seismic unit will void the certification of the unit. All mounting details li

Page 55

43 Figure 16 - Seismic Solid Bottom Curb without Filters Cross Section Figure 17 - Seismic Solid Bottom Curb without Filters Detail A Figure 18

Page 56

44 Figure 19 - Seismic Rigid Mount Curb

Page 57

45 Condenser Hail Guards 90-140 ton Units Condenser hail guards fold down and become a condenser coil shipping cover on 90-140 ton RN Series un

Page 58

46 Figure 21 - 90-140 ton Condenser Coil Guard Installation Instructions 2 Outside Air Rain Hood Rain hood must be opened before startup of the un

Page 59

47 Attach the side pieces to the top of the hood using the provided screws and attached the side pieces to the end of the unit through the flange. A

Page 60

48 Failure to attach and seal the end of unit with the flashings may result in water leakage into the curb. Figure 25 - Factory Suppl

Page 61

49 Electrical Verify the unit nameplate agrees with power supply. Connect power and control wiring to the unit as shown in Figure I12 and in the uni

Page 62

5 Index of Tables and Figures Tables: Table 1 - Electric and Gas Heating Capacities ...

Page 63

50 Figure 29 - Front View of Utility Entry and Power Switch from Control Compartment (55, 65 and 75-140 ton Units) Size supply conductors based

Page 64

51 Wire control signals to the unit’s low voltage terminal block located in the controls compartment. If an

Page 65

52 Total Wire Distance Allowable = (Quantity of Control Wires) x (Control Wire Distance) Take the total wire distance allowable and divide by

Page 66

53 Table 13 - 55, 65 and 75-140 ton Gas Connections Model Option B2 Input MBH Connections Quantity Size M 800 2 1” NPT N 1600 2 1-1/2” NPT P 2400 Af

Page 67 - Flat surface

54 Do not use gas piping smaller than unit gas connections. Natural gas pipe runs longer than 20 feet and propane gas pipe runs longer t

Page 68

55 Table 16 - Gas Piping Supports Pipe Size Support Intervals 1/2” to 3/4” Every 6 ft 3/4” to 1” Every 8 ft 1-3/4” or Larger (Horizontal) Every 10 ft

Page 69

56 Figure 31 - Example 6-25 and 30 ton through the Base Gas Piping Leak Testing All components of gas supply system, including manual shut

Page 70

57 All gas fired heat exchangers are completely tested at the factory before shipment. This will remove nearly all of the oils that have been

Page 71 - Startup

58 Refrigerant-to-Water Heat Exchanger Condenser water pump, condenser water piping, cooling tower or geothermal loop, pressure gauges, stra

Page 72

59 Freezing Water in the Heat Exchanger This product contains one or more refrigerant-to-water heat exchangers. A refrigerant

Page 73 - Bushing

6 Table 42 - 55, 65, and 75 ton Unit Filters ... 98 Table 43 - 90-1

Page 74

60 unit can operate without damaging unit components. Table 18 - Standard Brazed Plate Heat Exchanger Water Connections Model

Page 75

61 used as concentrated chemicals can cause corrosion. Never use hydrochloric acid (muriatic acid) or chlorine as it will corrode stainless

Page 76

62 penetrate the roof external to the unit itself. The drain line should be pitched away from the unit at least 1/8 inch per foot. On longer runs an

Page 77

63 Electric Preheat The modulating electric preheat option is designed to temper the incoming outside air to the unit based on an enabl

Page 78

64 proper operation efficiency and building occupant comfort. Normal maintenance requires periodic inspection of filters, the cassette

Page 79 - Gas Heater Instructions

65 Confirm that the wheel rotates freely. Apply power to the unit and confirm rotation. Airflow Balancing and Checking High performance systems comm

Page 80

66 adsorb and desorb moisture and also build up so as to reduce airflow. In a reasonably clean indoor environment such as a school or

Page 81

67 ventilators. In each case, it is recommended that the following considerations be addressed: Accessibility The cassette and all its operativ

Page 82 - Operation

68 Diameter Seal Adjustment Hub Seal Adjustment Service Segment Installation & Replacement Wheel segments are secured to the

Page 83

69 center of the wheel and inwards against the spoke flanges. If hand pressure does not fully seat the segment, insert the flat tip of a screw

Page 84 - Maintenance

7 Figure 35 - RET with Pin in Groove 4 ... 73 Figure 36 - Fan

Page 85

70 12. Apply power to wheel and ensure that the wheel rotates freely without interference. Belt Replacement

Page 86

71 Startup (See back of the manual for startup form.) During startup, it is necessary to perform routine checks on the p

Page 87

72 Figure 32 - Supply Fan Banding Power Return Axial Flow Fans (16-25 and 30 tons) Blade Pitch Angle Setting Instructions Step 1: Determin

Page 88

73 Figure 33 - Fan with the HUB on the Top and RET on the Bottom Step 3: Determine the direction of rotation Right, R, is clockwise when facin

Page 89

74 Step 7: Determine the current blade pitch and the pin location for the new blades Table 23 - Pin Location Type Bushing Mount Blade Pitch Angl

Page 90

75 Step 4: Remove the fan blades and replace the pitch pins Figure 39 - Pin Groove Location Figure 40 - Pitch Pin Location Figure 41 - Example

Page 91

76 Before Charging Unit being charged must be at or near full load conditions before adjusting the charge. Units equipped with hot gas re

Page 92

77 Table 25 - Acceptable Refrigeration Circuit Values Air-Cooled Cond./Air-Air Heat Pump Sub-Cooling 12-18°F Sub-Cooling with Hot Gas Reheat 15-22°

Page 93

78 Table 26 - R-410A and R-22 Refrigerant Temperature-Pressure Chart PSIG PSIG PSIG PSIG PSIG (F) R-410A R-22 (F) R-410A R-22 (F) R-410A R-2

Page 94

79 Gas Heater Instructions Figure 42 - Gas Heater Instructions

Page 95

8 Safety ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD Failur

Page 96

80 Condenser Fan Electronically Commutated Motor (ECM) Startup The fan cycling option uses a fan cycle switch to switch between one of the dis

Page 97

81 VFD Controlled Condenser Fan Startup With Customer Provided Unit Controls the VFD’s are factory provided and factory programmed. VFD’s rec

Page 98

82 Operation Unit operations should be controlled with thermostat, or unit controller, never at the main power supply, except for se

Page 99

83 Electric Heating Operation When a call for heating (G and W1, W2, etc.) is made the supply blower motors and electric resistance heaters

Page 100

84 Maintenance (See back of the manual for maintenance log) At least once each year, a trained, qualified service technician should check out

Page 101

85 If induced draft blower/motor assembly has to be replaced, care must be taken to provide an airtight seal between the blower housing and the burne

Page 102

86 Condenser Fans (6-25 and 30 ton) Condenser fans and motors can be removed and reinstalled as individual assemblies. Removal T

Page 103

87 Evaporator Coil (6-25 and 30 ton) Removal Evacuate refrigerant from the systems. Remove the TXV bulbs from the suction lines. Disc

Page 104

88 normal flow rate, preferably in a back-flush mode. After cleaning, the heat exchanger must be rinsed with clean water. A solution of 1-2% s

Page 105

89 chloride remover to remove soluble salts and revitalize the unit. Recommended Coil Cleaner The following cleaning agent, assuming it is used in

Page 106

9 FIRE, EXPLOSION OR CARBON MONOXIDE POISONING HAZA

Page 107

90 Supply Fans Lubrication All original fan motors and bearings are furnished with factory lubrication. Some applicat

Page 108

91 the inlet. A screw driver or crowbar can be used to help accomplish this. Use the pry slots on the back side of the motor mount. Pull the

Page 109 - RN Series Startup Form

92 4. On/Off LED = Alt. G/R Flashing Phase Loss LED = Green 5. On/Off LED = Green Phase Loss LED = Green Powering up with no voltage present: 1. On

Page 110

93 pattern according to the capacity demand signal of the system. The following table shows the linear relationship between the deman

Page 111

94 filters must point towards the blower. (RAB = Return Air Bypass, PE = Power Exhaust and PR = Power Return) Table 29 - 6-8 and 10 ton Pre Filt

Page 112

95 Table 33 - 50, 60, and 70 ton Pre Filters Feature 6A Quantity / Size Type 0 No Pre Filters A 24 / 12” x 24” x 2” Pleated, 30% Eff, MERV 8 B 6 / 1

Page 113 - Maintenance Log

96 Table 36 - 6-8 and 10 ton Unit Filters Feature 6B Quantity / Size Type 0 4 / 16” x 20” x 2” Pleated, 30% Eff, MERV 8 with RAB, Feature A2 = Q, R 2

Page 114 - Literature Change History

97 Table 38 - 13 and 15 ton Unit Filters Feature 6B Quantity / Size Type 0 4 / 20” x 25” x 2” Pleated, 30% Eff, MERV 8 with RAB, Feature A2 = Q, R 6

Page 115

98 Table 40 - 26, 31, and 40 ton Unit Filters Feature 6B Quantity / Size Type 0 8 / 24” x 24” x 2” Pleated, 30% Eff, MERV 8 with RAB, Feature A2 = Q,

Page 116

99 Table 43 - 90-140 ton Unit Filters Feature 6B Quantity / Size Type 0 35 / 18” x 20” x 2” Pleated, 30% Eff, MERV 8 B 21 / 20” x 24” x 4” & 7 /