Aaon CL-230 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Adoucisseurs Aaon CL-230. AAON CL-230 User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 54
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
CL SERIES
ROOFTOP CONDENSING UNITS
INSTALLATION, SERVICE
&
OWNER’S INFORMATION MANUAL
Vue de la page 0
1 2 3 4 5 6 ... 53 54

Résumé du contenu

Page 1 - CL SERIES

CL SERIES ROOFTOP CONDENSING UNITS INSTALLATION, SERVICE & OWNER’S INFORMATION MANUAL

Page 2 - TABLE OF CONTENTS

10 Diagram of Evaporative-cooled condenser Section including field water connections and base cutout tap

Page 3

11STARTUP Pre-Startup: After the installation and immediately before the startup of the condenser be sure that these items have been checked. 1. Ve

Page 4

12STARTUP cont. Step 2. Find Blade Pitch Angle: ( 20, 25, 27.5, 30, 32.5, 35, 37.5, 40, 45 or 50 ) • Carefully disassemble fan on flat surface and n

Page 5 - INSTALLATION

13STARTUP cont. Step 3. Determine blade rotation – on the concave side of the blade is a blade marking showing 6WR, 6WL, 7WL, 7WR, or 9WR. The “L”

Page 6 - INSTALLATION cont

14SERVICING AND MAINTENANCE cont. Charging Refrigerant: • Charging a system in the field must be based on determination of liquid sub-cooling and ev

Page 7

15SERVICING AND MAINTENANCE cont. Adjusting Sub-cooling and Superheat Temperatures: The system is overcharged if: 1. the sub-cooling temperature is

Page 8

16AAON, Inc. www.aaon.com Customer Service Department 2425 South Yukon Ave • Tulsa, OK 74107 Phone: 918-583-2266 • Fax: 918-382-6364 ALWAYS USE AAON

Page 9

17EVAPORATIVE-COOLED CONDENSER cont. Performance: Improper location of the evaporative-cooled condenser may seriously degrade the capacity of the

Page 10

18EVAPORATIVE-COOLED CONDENSER cont. 4. Turn rotating element by hand to assure that it rotates freely. Running: Periodically inspect pump while r

Page 11 - STARTUP

19EVAPORATIVE-COOLED CONDENSER cont. Water Treatment System: • All AAON evaporative-cooled condensers come equipped with a water treatment system th

Page 12 - STARTUP cont

2TABLE OF CONTENTS SECTION Page GENERAL DESCRIPTION………………………………………………………………………………………………… Unpacking…………………………………………………………………………………………………………..04 04 OW

Page 13 - SERVICING AND MAINTENANCE

20EVAPORATIVE-COOLED CONDENSER cont. MAINTENANCE RECOMMENDATIONS Pump Maintenance: • Cleaning - Remove oil, dust, water, and chemicals from exterio

Page 14

21EVAPORATIVE-COOLED CONDENSER cont. WATER QUALITY Recirculating Water Quality Guidelines: • Cycles of concentration (the ratio of dissolved soli

Page 15

22REFRIGERANT PIPING cont. • Excessive suction line pressure drop causes loss of compressor capacity and increased power usage resulting in reduced

Page 16 - AAON, Inc

23REFRIGERANT PIPING cont. • If the velocity of refrigerant in the liquid line is too great, it could cause excessive noise or piping erosion. The r

Page 17 - CONDENSER cont

24REFRIGERANT PIPING cont. Hot Gas Bypass Line: • Hot Gas Bypass is available for use with DX systems that may experience low suction pressure durin

Page 18

25REFRIGERANT PIPING cont. (ASHRAE Handbook 2006 - Refrigeration p. 2.19). Hot gas bypass pipe diameters are selected to maintain velocity below a

Page 19

26REFRIGERANT PIPING cont. TABLE RP-1 Predetermined Line sizes for Dual Circuit CL units with R-410A Tons System R-410A Connection Size Predetermin

Page 20

27REFRIGERANT PIPING cont. TABLE RP-2 Predetermined Line sizes for Dual Circuit CL units with R-22 Tons System R-22 Connection Size Predetermined L

Page 21

28REFRIGERANT PIPING cont. TABLE RP-3 Predetermined Line sizes for Single Circuit CL units with R-410A Tons System R-410A Connection Size Predeterm

Page 22 - REFRIGERANT PIPING cont

29REFRIGERANT PIPING cont. FIGURE RP-1. Riser height versus total equivalent line length for R-410A split system applications with dual circuited CL

Page 23

3 It is the intent of AAON, Inc. to provide accurate and current specification information. However, in the interest of product

Page 24

30REFRIGERANT PIPING cont. FIGURE RP-3. Riser height versus total equivalent line length for R-410A split system applications with single circuited

Page 25

31 FIGURE RP-2. Hot Gas Bypass Piping Diagram with air handler above condenser. Note: Components shown within air handler and condensing unit are fac

Page 26

32 FIGURE RP-3. Hot Gas Bypass Piping Diagram with air handler below condenser. Note: Components shown within air handler and condensing unit are fa

Page 27

33 FIGURE RP-4. Hot Gas Reheat Piping Diagram with air handler above condenser. Note: Components shown within air handler and condensing unit are f

Page 28

34 FIGURE RP-5. Hot Gas Reheat Piping Diagram with air handler below condenser. Note: Components shown within air handler and condensing unit are fa

Page 29

35 FIGURE RP-6. Hot Gas Reheat Piping Diagram with air handler above condenser and field installed suction line accumulator. Note: Components shown w

Page 30

36 FIGURE RP-7. Hot Gas Reheat Piping Diagram with air handler above condenser and field installed suction line accumulator. Note: Components shown w

Page 31

37 FIGURE RP-8. Reheat/Hot Gas Bypass Piping Diagram with air handler above condenser. Note: Components shown within air handler and condensing unit

Page 32

38 FIGURE RP-9. Reheat/Hot Gas Bypass Piping Diagram with air handler below condenser. Note: Components shown within air handler and condensing unit

Page 33

39 FIGURE RP-10. Reheat/Hot Gas Bypass Piping Diagram with air handler evaporator above condenser and field installed suction line accumulator. Note:

Page 34

4GENERAL DESCRIPTION All AAON 'CL Series' condensers are factory assembled, wired, and charged with 15 lbs. of refrigerant per system. Mod

Page 35 - TO BE INSTALLED IN FIELD

40 FIGURE RP-11. Reheat/Hot Gas Bypass Piping Diagram with air handler below condenser and field installed suction line accumulator.Note: Components

Page 36

41 FIGURE RP-5. Hot Gas Bypass Piping Diagram with air handler above condenser. Note: Components shown within air handler and condensing unit are fac

Page 37

42 FIGURE RP-6. Hot Gas Bypass Piping Diagram with air handler below condenser. Note: Components shown within air handler and condensing unit are fa

Page 38

43 FIGURE RP-7. Hot Gas Reheat Piping Diagram with air handler above condenser. Note: Components shown within air handler and condensing unit are f

Page 39

44 FIGURE RP-8. Hot Gas Reheat Piping Diagram with air handler below condenser. Note: Components shown within air handler and condensing unit are fa

Page 40

45 FIGURE RP-9. Hot Gas Reheat Piping Diagram with air handler above condenser and field installed suction line accumulator. Note: Components shown w

Page 41

46 FIGURE RP-10. Hot Gas Reheat Piping Diagram with air handler above condenser and field installed suction line accumulator. Note: Components shown

Page 42

47 FIGURE RP-11. Reheat/Hot Gas Bypass Piping Diagram with air handler above condenser. Note: Components shown within air handler and condensing unit

Page 43

48 FIGURE RP-12. Reheat/Hot Gas Bypass Piping Diagram with air handler below condenser. Note: Components shown within air handler and condensing unit

Page 44

49 FIGURE RP-13. Reheat/Hot Gas Bypass Piping Diagram with air handler evaporator above condenser and field installed suction line accumulator. Note:

Page 45

5OWNER'S INFORMATION cont. General Maintenance: When the initial startup is made and on a periodic schedule during operation, it is necessary t

Page 46

50 FIGURE RP-14. Reheat/Hot Gas Bypass Piping Diagram with air handler below condenser and field installed suction line accumulator.Note: Components

Page 47

Condenser and Condenser Unit Startup Form Date:______________ Job Name:_____________________________________________________________________ Address

Page 48

Refrigeration System 1 Pressure Saturated Temperature Line Temperature Sub-cooling Superheat Discharge N/A N/A Suction N/A Liquid N/A Ref

Page 49

Maintenance Log This log must be kept with the unit. It is the responsibility of the owner and/or maintenance/service contractor to document any serv

Page 50

CL SERIES CONDENSING UNIT • INSTALLATION, SERVICE & OWNERS INFORMATION MANUAL AAON, Inc. 2425 South Yukon Tulsa, Oklahoma 74107

Page 51

6INSTALLATION cont. low, there will be insufficient pressure to operate the expansion valve properly. During low ambient temperatures, it is diffic

Page 52

7INSTALLATION cont. OROA Valve: This system uses a nonadjustable head pressure control valve that performs the function of limiting the flow of liq

Page 53

8INSTALLATION cont. Piping Schematic of Example system using the ORI/ORD valve. The pressure setting of the ORI valve determines how well the syst

Page 54 - CL SERIES CONDENSING

9INSTALLATION cont. During higher ambient temperatures the entire condenser is required to condense refrigerant. During these higher ambient temper

Commentaires sur ces manuels

Pas de commentaire